1) FYI, you posted in the 'Murican section, rather than the Canadian section.Thanks for your response. What's Murican section? Where can I find Canadian section? Your fire protection engineer is going to design the cistern and associated fire pump requirements. People who are not skilled in this design should not attempt it. Your post does not have anywhere near the information necessary to perform the calculation.
2) Variances are for property uses (zoning), not building code. You may be thinking of alternative solutions.
3) Supply rates are in standards like NFPA 13, NFPA 20, etc. The sprinkler designer will tell you what is required, based on the design of the sprinkler, he building occupancy and other variables.
Generally speaking, the requirement is to be able to supply all on-site firefighting demands for one hour for low-risk occupancy, two hours for others. 60,000 gallons (272,000 litres may be enough. May not.) I had a similar project that *had* access to town water, but the flow rates weren't enough so they build a fire pond.
Note that NBC allows for "water on site" to suffice for firefighting efforts. I have a lobster-holding facility that's located 30 metres from the ocean. Building didn't require a sprinkler, and the ocean (and lobster tanks) are "sufficient water onsite." Also nicely salinated, so no worry about freezing. Pain in the tush on the firefighting gear, but code doesn't say the water can't be the ocean.
Your fire protection engineer is going to design the cistern and associated fire pump requirements. People who are not skilled in this design should not attempt it. Your post does not have anywhere near the information necessary to perform the calculation.Thanks for your input. What information is needed to perform the calculation as per the building code?
Plumbing demand will come from the plumbing code. Your mechanical engineer will be able to properly size the demand for the domestic water supply. Again, your post is lacking necessary information to perform the calculation.
I've never seen a situation where the fire and domestic water supply have been from the same system. Even connecting to municipal systems, there is usually a fire and domestic line that is run in from the water main.